Boston Scientific reduced energy and maintenance costs with DriSteem electric humidifiers
Results:
• Achieved payback within 1.8 years
• Achieved relative humidity (RH) set point within 1%
• Reduced humidifier energy costs by 38%
• Reduced humidifier operating costs by 55%
• Reduced humidifier maintenance costs by 90%
Cork, Ireland
Challenge: Improve Control & Efficiency
Boston Scientific–Cork Ltd. (BSCL) manufactures stents for heart surgery patients. This critical application requires humidification delivered 24 hours a day continuously within 1% of set point. However, existing humidifiers were not meeting this control requirement. Additional challenges included reducing energy and maintenance costs, increasing reliability, and meeting a two-year or less payback required for funding.
Application: Match Humidifier to Requirements
BSCL had seven air handling units with previously installed electrode humidifiers operating with very hard, potable water, and dispersing steam through multiple dispersion units. Electrode technology is suitable for a number of humidification applications. However, it is not applicable for critical applications requiring continuous operation and tight control, or applications where reduced maintenance costs and resource conservation are a priority.
Electrode technology requires frequent draining, filling, and reheating in order to maintain steam production. Noncontinuous steam production makes tight control difficult. Therefore, BSCL experienced frequent interruptions in steam production, higher energy costs from reheating, more water usage due to refilling, and higher maintenance costs due to cylinder replacement.
Solution
Fourteen DriSteem resistive-element Vapormist® humidifiers were installed in BSCL’s stent production areas replacing the existing electrode humidifiers. All of the Vapormist humidifiers maintained RH within 1% of set point for BSCL’s production rooms, as required. Rapid-sorb dispersion panels dispersed the steam in the seven air handlers. The humidifiers were distributed throughout the air handling units, and depending on the load, some air handling units had three humidifiers.
Heating fresh water to replace drained water (to remove conductive ions), can affect electrode humidifier performance and efficiency. Resistive technology combined with RO/DI water provided the tight control and minimal maintenance that BSCL was looking for. Properly maintained RO/DI water does not require draining or skimming, and resistive technology with RO/DI water allows for continuous steam production.
Cost Savings Breakdown
• Energy costs: Reduced the need for heating make-up water, saved 38%.
• Maintenance costs: No cylinders to be replaced or refurbished, saved 90%.
• Operating costs: Energy and maintenance costs combined for an overall reduction in run time, saved 55%.
DriSteem Distributor, Intelligent Building Controls Ltd. (IBC), is the premier supplier of top quality building energy management systems, control and measurement products in Dublin, Ireland. IBC provided superb consultation to BSCL throughout the duration of this project.
PM Group was instrumental in their system design. PM Group was established in 1973 and has grown to become one of the most respected engineering design, architecture and project management firms in the world. Envotech was important for their partnership and innovation. Envotech’s growth is spurred by innovative products, intelligent designs, and custom projects fueled by collaboration.
Resources
Metric Version of the Case Study
Learn about the following equipment installed at Boston Scientific – Cork Ltd.:
Start a Project
Expert Partner: A local DriSteem rep will work with your facilities team to identify the best solutions available for your application. They will review existing systems and spaces to determine the best way to reach the ideal RH range to improve processes and protect your valuable equipment, materials, and people.